Let's take a look at the types and features of representative DCS protocols (Yokogawa, Honeywell & Emerson)



OT protocol used in OT sites (
Oil&Gas/Refining/Chemical/Power Generation etc.) where DCS is the main focus



DCS Protocols of Yokogawa, Honeywell, and Emerson

VendorProtocolTCP/UDPRemarkEncryption
YokogawaVnet/IPUDP 12345High-speed, deterministic redundant network for process control. Uses Layer 2 switching.No native
YokogawaEthernet-based FCS (Field Control Station) ProtocolTCP 8888Proprietary protocol used for communication between control stations and operator terminals.No
YokogawaFF-H1 (FOUNDATION Fieldbus H1)Serial (31.25 kbps)Digital, two-way communication for field devices and process instruments.No
YokogawaFF-HSE (FOUNDATION Fieldbus High-Speed Ethernet)TCP/IP-basedHigh-speed, Ethernet-based backbone for process automation networks.No
YokogawaModbus TCP/IPTCP 502Industry-standard master-slave protocol for data exchange.No
HoneywellExperion Control Network (ECN)TCP/UDP (proprietary)Used for Experion PKS (Process Knowledge System). Supports redundant communication.No native
HoneywellSafety Manager ProtocolTCP/UDP (proprietary)Used for Honeywell Safety Instrumented Systems (SIS). Integrated into Experion DCS.No native
HoneywellModbus TCP/IPTCP 502Master-slave protocol for third-party device integration.No
HoneywellOPC UA (for Experion)TCP 4840Secure protocol with structured data modeling for interoperability.Encrypted (TLS, certificates)
EmersonDeltaV Control NetworkUDP 18520Proprietary deterministic control network with redundant switching for high reliability.No
EmersonOPC UA (for DeltaV)TCP 4840Uses secure data modeling for interfacing third-party systems.Encrypted (TLS, certificates)
EmersonEtherNet/IP (for DeltaV)TCP 44818 / UDP 2222Uses CIP (Common Industrial Protocol) for cyclic messaging.No by default, but TLS available
EmersonHART (Highway Addressable Remote Transducer)Serial (Bell 202) / TCPDigital-over-analog 4-20mA protocol. Common in instrumentation and valve control.No
EmersonPROFINETTCP 34962-34964 / UDP 34962Uses Real-Time (RT) & Isochronous Real-Time (IRT) for industrial automation.No

Recap

  • Yokogawa uses Vnet/IP for high-speed deterministic control, while Emerson uses DeltaV Control Network and Honeywell uses ECN.
  • Honeywell's Experion DCS and Emerson’s DeltaV DCS support OPC UA for secure interoperability.
  • Most traditional DCS protocols lack encryption, except for OPC UA and some secure EtherNet/IP implementations.
  • FOUNDATION Fieldbus and HART are widely used across all three vendors for field device communication.

#CPS #OT #XIoT #IoT #IIoT #IoMT #CPSSecurity #OTSecurity #IoTSecurity #CPS보안 #OT보안 #IoT보안

Comments

Popular posts from this blog

Don't confuse DCS, PLC and SCADA in front of OT specialists

Top 20 Threat Scenarios & Playbooks for OT Security

Let's create our own ICS Labs in the VMs!